Vertiv™ CoolChip CDU
Designed to support liquid cooling within high density environments, the Vertiv CoolChip CDU is the next generation of coolant distribution units. They are suitable for direct-to-chip and rear door cooling applications that offer easy, cost-effective deployment in any data center. The CoolChip CDU family offers multiple system designs that operate with and without access to facility water, allowing you to tap into the benefits of liquid-cooled servers to more efficiently support higher rack densities. Select between in-rack, in-row, or perimeter-based designs as well as liquid-to-liquid or liquid-to-air heat exchangers.
Zapisano produkt na tablicy użytkownika
Zapisano produkt na tablicy użytkownika, aby móc wrócić do niego w przyszłości. Jeśli nie chcesz tego przedmiotu w zapisanych, można z łatwością usunąć go z tablicy użytkownika.
Zaloguj się lub załóż konto, aby zapisać to na później
- Data Center/Colocation/Hosting
- Education
- Government
- Healthcare
- Retail and Wholesale
Vertiv™ CoolChip CDU
Designed to support liquid cooling within high density environments, the Vertiv CoolChip CDU is the next generation of coolant distribution units. They are suitable for direct-to-chip and rear door cooling applications that offer easy, cost-effective deployment in any data center. The CoolChip CDU family offers multiple system designs that operate with and without access to facility water, allowing you to tap into the benefits of liquid-cooled servers to more efficiently support higher rack densities. Select between in-rack, in-row, or perimeter-based designs as well as liquid-to-liquid or liquid-to-air heat exchangers.
- Data Center/Colocation/Hosting
- Education
- Government
- Healthcare
- Retail and Wholesale
Specyfikacja techniczna
As data centers adopt liquid cooling, fitting in new coolant distribution infrastructure can be a real challenge. From hyperscale and colocation environments to edge applications, the Vertiv™ CoolChip CDU (the next generation of the Liebert® XDU family) simplifies your work with the flexibility to support rear door heat exchangers or direct to chip liquid cooling. The Vertiv CoolChip CDU’s compact footprint allows for in-rack, end of row, or perimeter placement options. However, and wherever you incorporate the Vertiv CoolChip CDU, you can easily distribute coolant to efficiently manage power-dense hot spots with liquid-to-liquid heat exchange up to 100 kw, 450 kW, 600 kW, or 1,350 KW, and liquid-to-air heat exchange up to 70kW. The Vertiv CoolChip CDU provides a compact footprint for deployment flexibility, efficient coolant distribution to manage power dense hot-spots, precise temperature control to eliminate thermal shock, redundant pumps and dual power feeds for reliable operation, and remote monitoring and communications for added peace of mind.
|
Vertiv™ CoolChip CDU 70
|
|||||
|---|---|---|---|---|---|
| 70.0 kW at 11C approach temperature difference | 10,100 m3/h (5,945 CFM) | 91 in | 24 in | 48 in | 899 lbs |
| Zobacz więcej informacji o produktach | |||||
|
Liebert® XDU1350 Coolant Distribution Unit
|
|||||
| 1368 kW at 7.2°F (4°C) | N/A | 684 in | 35.4 in | 48.9 in | 1431 lbs |
| Zobacz więcej informacji o produktach | |||||
|
Vertiv™ CoolChip CDU, 100
|
|||||
| 101 kW at 7.2⁰F (4⁰C) approach temperature difference | N/A | 6.8 in; 4RU | 17.5 in | 34.2 in | 130 lbs |
| Zobacz więcej informacji o produktach | |||||
|
Vertiv™ CoolChip CDU 600
|
|||||
| 600kW at 7.2 F (4.0 C) approach temperature difference | N/A | 78.7 in | 23.6 in | 47.2 in | 1058 lbs |
| Zobacz więcej informacji o produktach |
Korzyści
Właściwości
- Vertiv™ CoolChip CDU 70 Application and Planning Guide SL-80015
- Vertiv™ CoolChip CDU 70 Operation and Maintenance Guide SL-80016
- Vertiv™ CoolChip CDU 70 Installation and Commissioning Guide SL-80017
- Vertiv™ CoolChip CDU 121 Application and Planning Guide SL-80276
- Vertiv™ CoolChip CDU 121 Installation and Commissioning Guide SL-80277
- Vertiv™ CoolChip CDU 121 Operation and Maintenance Guide SL-80278
- Vertiv™ CoolChip CDU 600 Application and Planning Guide SL-07624
- Vertiv™ CoolChip CDU 600 Installation and Commissioning Guide SL-07625
- Vertiv™ CoolChip CDU 600 Operation and Maintenance Guide SL-07626
- Vertiv™ Liebert® XDU1350 Installation and Commissioning Guide SL-71308
- Vertiv™ Liebert® XDU1350 Application and Planning Guide SL-71309
- Vertiv™ Liebert® XDU1350 Operation and Maintenance Guide SL-71310
- Guidelines for Deployment of Single Phase Technology Cooling System SL-80056.pdf