Releases for Vertiv Liebert GXT5 VRLA UPS 500-3KVA (LV, HV, I)
GXT5-500LVRT2UXL, GXT5-750LVRT2UXL, GXT5-1000LVRT2UXL(TAA), GXT5-1500LVRT2UXL(TAA), GXT5-2000LVRT2UXL(TAA), GXT5-3000LVRT2UXL(TAA), GXT5-750IRT2UXL, GXT5-750IRT2UXLE, GXT5-1000IRT2UXL, GXT5-1000IRT2UXLE, GXT5-1500IRT2UXL, GXT5-1500IRT2UXLE, GXT5-2000IRT2UXL, GXT5-2000IRT2UXLE, GXT5-3000IRT2UXL, GXT5-3000IRT2UXLE, GXT5-3KL620RT2UXL, GXT5-3KL630RT2UXL
NOTE: Each release includes all the updates from previous releases. If upgrading a firmware version that is several releases old, it is only necessary to install the latest. For detailed instructions refer to the user guide.
| RELEASE DATE |
PRODUCT FAMILY |
VERSION |
DOWNLOAD |
| MCU |
DSP |
January 2025
|
500-3kVA (LV, HV, I) |
V250 |
V220 |
GXT5LA (500-3K LV,HV,I) 2025-jan.zip + -
|
Release Notes:
- Updated the USB HID protocol mapping to mimic the GXT4 models
- Changed the default setting of "start with no battery" to ENABLED
- Improved the battery test feature to address multiple battery models
- Enabled the Auto-restart feature to function with no battery detected
- Removed the Line-Neutral reversal detection only for the "I" models
|
October 2023
|
500-3kVA (LV, HV, I) |
V240 |
V210 |
GXT5LA (500-3K LV,HV,I) 2023-Oct.zip + -
|
Release Notes:
- Improved battery charging logic to automatically set the charge current and temperature compensation
- Improved battery test logic accuracy for both automatic & manual tests for all load levels
- Fixed a minor security vulnerability in the CLI interface
|
October 2022
|
500-3kVA (LV, HV, I) |
V230 |
V200 |
GXT5LA (500-3K LV,HV,I) 2022-Oct.zip + -
|
Release Notes:
- Added MODBUS RTU protocol integrated as standard for all GXT5 VRLA models.
|
May 2022
|
500-3kVA (LV, HV, I) |
V210 |
V190 |
GXT5LA (500-3K LV,HV,I) 2022-May.zip + -
|
Release Notes:
- Improved RDU101 web-interface active events log by removing "UPS Output on Inverter" alert.
|
November 15, 2021
|
500-3KVA (LV, HV, I) |
V200 |
V190 |
GXT5(500-3K)(LV,HV,I)2021-11-15.zip + -
|
Release Notes:
- Added all UPS status and setting datapoints available on the LCD to the RDU101 web-interface and SNMP/other protocols.
- Added a new user-configurable alarm, "Replace Battery Soon", which can be set to alert the user 2, 3, or 4 months before the time the UPS calculates a new battery will be needed, allowing time for replacement batteries to be ordered.
- Added the ability to adjust [Discharge protect time] and [Guaranteed Shutdown] settings on the CLI.
- Improved the downloadable 'Event Log.csv' by replacing the catch-all "General Unspecified Event" with each UPS alarm as reported on the UPS LCD.
- Fixed an intermittent communication issue between RDU101 and UPS.
|
October 12, 2020
|
500-3KVA (LV, HV, I) |
V190 |
V190 |
GXT5(500-3K)(LV,HV,I)2020-10-12.zip + -
|
Release Notes:
- Enhanced the security of the firmware update procedure by using encrypted firmware files. This prevents the use of potentially non-authentic firmware.
- Improved the [Max charge curr] setting to only show valid options for the installed UPS/EBC configuration.
- Added the ability to change the LCD settings menu and maintenance menu passwords via the CLI.
- Added the ability to execute a delayed shutdown from 0-999 seconds via the CLI.
- Added Czech language option to the LCD.
- Improved the fan performance by making the speed more stable and smoothing the transition between speeds.
- Added the DSP firmware kernal version number to the LCD About tab.
- Changed the setting name of [Temperature type] to [Temperature unit].
- Changed the default temperature display from °C to °F for HV, MV, and LV models.
- Increased the low line transfer point on GXT5-3KL620 and GXT5-3KL630 models from 160V to 176V to prevent the input breaker from tripping during a low-line condition at 105% load for an extended period of time.
|
May 30, 2020
|
500-3KVA (LV, HV, I) |
V180 |
V180 |
GXT5(500-3K)(LV,HV,I)2020-05-30.zip + -
|
Release Notes:
- Increased the power rating of the GXT5-3K620 from 2700W to 3000W.
- Expanded the output voltage selections on the 3KL620 and 3K630 models to 200/208/220/230/240VAC.
- Changed the user setting and factory default value of [guaranteed shutdown] to "disabled" to reflect the use-case of the majority of customers. See user guide for details on this setting.
- Changed the user setting and factory default value of [battery periodic test] to "enabled" to allow automatic battery self checks.
- Improved the behavior of [any mode shutdown] by checking the state of the dry contacts during power up after a utility outage and return. If the contacts are cleared during the outage, the UPS will now power back on automatically when the utility returns.
- Improved the complete UPS shutdown procedure by adding step-by-step instructions to the LCD when a full shutdown is initiated.
- Added a warning message to the RDU101 web interface showing when the UPS detects a disconnected external battery cabinet. (RDU101 v1.4 required.)
- Added support for Vertiv's new Power Assist tool.
- Improved the responsiveness of the status updates reported through the USB HID / Windows OS.
- Added ability to switch the temp readings from C to F.
- Added Italian language to the LCD.
- Changed the name the setting [Battery replacement time] to [Battery Last Replaced] and updated the default time from 2017-12-14:00:00:00 to the date/time of production.
- Corrected the issue where "unavailable" was being displayed in the [battery temperature] field in the RDU101 web interface.
- Added legacy GXT4 datapoints to the RDU101 interface: BatteryCharger, BatteryFloatVoltage, DeviceManufactureDate. (RDU101 v1.4 required.)
|
November 30, 2019
|
500-3KVA (LV, HV, I) |
V170 |
V170 |
GXT5(500-3K)(LV,HV,I)2019-11-30.zip + -
|
Release Notes:
- Added the ability to detect within two minutes a missing internal battery when no EBCs are in use.
- Updated the factory default setting for battery charging temperature compensation [temp compensation] from disable to enabled. Note: This does not change the user setting, just the factory default setting.
- Improved the firmware update method by eliminating the connected EBC notification after each update.
- Improved the firmware update method by removing the [UPS has no output] alarm that the user had to clear after each update.
- Added to the command line interface reporting of the number of external battery cabinets.
- Added to the command line interface ability to set a static IP address on the RDU101 interface.
- Updated the command line interface so the format of the discharge time is consistent with the LCD; XX hr XX min.
- Added to the RDU101 interface the reporting of the UPS alarm [Battery Not Qualified].
- Updated the RDU101 interface to report the UPS ambient temperature.
- Increased the maximum number of possible connected external temperature sensors to 40.
- Improved the battery aging calculations by setting the default initial battery running time to 0 days after full-charge at factory.
- Added support for YDN23 communications protocol.
- Added support for GXT5-3000IRT2UXLN model
|
September 13, 2019
|
500-3KVA (LV, HV, I) |
V160 |
V160 |
GXT5(500-3K)(LV,HV,I)2019-09-13.zip + -
|
Release Notes:
- Added LCD pop-up notification message to detect if the number of external battery cabinets changes
|
May 15, 2019
|
500-3KVA (LV, HV, I) |
V150 |
V160 |
GXT5(500-3K)(LV,HV,I)2019-05-15.zip + -
|
Release Notes:
- Initial release. 500VA-3KVA (I, HV)
- Improved the quality of the battery charging current to allow for better charging performance.
- Improved the diagnostic alarm [auxiliary power fault].
- Updated the LCD displayed Chinese language shutdown and shutoff menus.
- Updated the RDU101 interface to allow external battery temperature sensors to be connected after power on.
- Updated the RDU101 interface flow screen to match LCD.
- Added to the command line interface ability to configure RDU101 network settings.
- Updated the command line interface to increase the login timeout from 1 minute to 3 minutes.
|
May 27, 2019
|
500-3KVA (LV, HV, I) |
V140 |
V150 |
N/A + -
|
Release Notes:
- Factory use only.
|
March 15, 2019
|
500-3KVA (LV, HV, I) |
V140 |
V140 |
N/A + -
|
Release Notes:
- Factory use only.
|
February 22, 2019
|
500-3KVA (LV, HV, I) |
V140 |
V130 |
GXT5(500-3K)(LV,HV,I)2019-02-22.zip + -
|
Release Notes:
- Initial release. 500VA-3KVA (LV)
|
Releases for Vertiv Liebert GXT5 VRLA UPS 5KVA-10KVA (MV)
GXT5-5000MVRT4UXLN, GXT5-6000MVRT4UXLN, GXT5-8000MVRT6UXLN,
GXT5-10KMVRT6UXLN, GXT5-6000RT208
NOTE: Each release includes all the updates from previous releases. If upgrading a firmware version that
is several releases old, it is only necessary to install the latest. For detailed instructions refer to
the user guide.
| RELEASE DATE |
PRODUCT
FAMILY |
VERSION |
DOWNLOAD |
| MCU |
DSP |
August 2026
|
5kVA-10kVA (MV) |
V270 |
V240 |
GXT5LA (5-10K MV) 2026-Aug.zip +
-
|
Release Notes:
- Improved VRLA battery test logic accuracy
and consistency for automatic and manual battery tests.
|
January 2025
|
5kVA-10kVA (MV) |
V250 |
V220 |
GXT5LA (5-10K MV)
2025-jan.zip +
-
|
Release Notes:
- Updated the USB HID protocol mapping to
mimic the GXT4 models
- Changed the default setting of "start with
no battery" to ENABLED
- Improved the battery test feature to address
multiple battery models
- Enabled the Auto-restart feature to function
with no battery detected
- Improved the transfer times for transfers
to/from inverter and bypass
|
October 2023
|
5kVA-10kVA (MV) |
V240 |
V210 |
GXT5LA
(5-10K MV) 2023-Oct.zip +
-
|
Release Notes:
- Improved battery charging logic to
automatically set the charge current and temperature compensation
- Improved battery test logic accuracy for
both automatic & manual tests for all load levels
- Fixed a minor security vulnerability in the
CLI interface
|
October 2022
|
5kVA-10kVA (MV) |
V230 |
V200 |
GXT5LA
(5-10K MV) 2022-Oct.zip +
-
|
Release Notes:
- Added MODBUS RTU protocol integrated as
standard for all GXT5 VRLA models.
- Improved battery test performance at all
load levels
|
May 2022
|
5kVA-10kVA (MV) |
V210 |
V190 |
GXT5LA
(5-10K MV) 2022-May.zip +
-
|
Release Notes:
- Improved RDU101 web-interface active events
log by removing "UPS Output on Inverter" alert.
|
November 15, 2021
|
5kVA-10kVA (MV) |
V200 |
V170 |
GXT5(5-10K)(MV)2021-11-15.zip
+
-
|
Release Notes:
- Added all UPS status and setting datapoints
available on the LCD to the RDU101 web-interface and SNMP/other protocols.
- Added a new user-configurable alarm,
"Replace Battery Soon", which can be set to alert the user 2, 3, or 4 months before the
time the UPS calculates a new battery will be needed, allowing time for replacement
batteries to be ordered.
- Added the ability to adjust [Discharge
protect time] and [Guaranteed Shutdown] settings on the CLI.
- Improved the downloadable 'Event Log.csv' by
replacing the catch-all "General Unspecified Event" with each UPS alarm as reported on
the UPS LCD.
- Fixed an intermittent communication issue
between RDU101 and UPS.
|
October 12, 2020
|
5KVA-10KVA (MV) |
V190 |
V170 |
GXT5(5-10K)(MV)2020-10-12.zip
+
-
|
Release Notes:
- Enhanced the security of the firmware update
procedure by using encrypted firmware files. This prevents the use of potentially
non-authentic firmware.
- Improved the [Max charge curr] setting to
only show valid options for the installed UPS/EBC configuration.
- Added the ability to change the LCD settings
menu and maintenance menu passwords via the CLI.
- Added the ability to execute a delayed
shutdown from 0-999 seconds via the CLI.
- Added Czech language option to the LCD.
- Improved the fan performance by making the
speed more stable and smoothing the transition between speeds.
- Added the DSP firmware kernal version number
to the LCD About tab.
- Improved the displayed load and runtime
sensitivity on light loads down from 5% to 2% load, on the 5K through 20K models.
(GXT5-5000MV, GXT5-6000MV, GXT5-8000MV, GXT5-10KMV)
- Changed the setting name of [Temperature
type] to [Temperature unit].
- Decreased the output rating of the
GXT5-6000MV when using a L14-30 corded optional POD from 5100W to 5000W to give margin
on 30A input breaker.
- Changed the default temperature display from
°C to °F for HV, MV, and LV models.
|
May 30, 2020
|
5KVA-10KVA (MV) |
V180 |
V160 |
GXT5(5-10K)(MV)2020-05-30.zip
+
-
|
Release Notes:
- Increased the power rating of the
GXT5-5000MVRT4UXLN from 4500W to 5000W and decreased the power rating of the
GXT5-6000MVRT4UXLN from 5400W to 5100W when used with an optional POD with a L14-30
input cord (PD5-001 to PD5-006).
- Changed the user setting and factory default
value of [Guaranteed Shutdown] to "disabled" to reflect the use-case of the majority of
customers.
- Changed the user setting and factory default
value of [Battery Periodic Test] to "enabled" to allow automatic battery self checks.
The default interval for battery self checks is 8 weeks, but this can be changed in the
settings menu.
- Improved the behavior of [Any Mode Shutdown]
by checking the state of the dry contacts during power up after a utility outage and
return. If the contacts are cleared during the outage, the UPS will now power back on
automatically when the utility returns.
- Improved the complete local UPS shutdown
procedure by adding step-by-step instructions to the LCD when a full shutdown is
initiated.
- Added a warning message to the RDU101 web
interface showing when the UPS detects a disconnected external battery cabinet. (RDU101
v1.4 required.)
- Added support for Vertiv's new Power Assist
tool.
- Improved the responsiveness of the status
updates reported through the USB HID / Windows OS.
- Added ability to switch the temperature
readings from C to F.
- Added Italian language to the LCD.
- Improved the LCD's flow screen on the
GXT5-MV units to show L1 and L2 separately.
- Changed the name of the setting [Battery
Replacement Time] to [Battery Last Replaced] and updated the default time from
2017-12-14:00:00:00 to the date/time of production.
- Corrected the issue where "unavailable" was
being displayed in the [Battery Temperature] field in the RDU101 web interface.
- Added legacy GXT4 datapoints to the RDU101
interface: BatteryCharger, BatteryFloatVoltage, DeviceManufactureDate. (RDU101 v1.4
required.)
|
November 30, 2019
|
5KVA-10KVA (MV) |
V170 |
V150 |
GXT5(5-10K)(MV)2019-11-30.zip
+
-
|
Release Notes:
- Updated the factory default setting for
battery charging temperature compensation [temp compensation] from disable to enabled.
Note: This does not change the user setting,
just the factory default setting.
- Improved the DSP firmware update method so
that EPO connector does not have to be pulled out during update.
- Improved the firmware update method by
eliminating the connected EBC notification after each update.
- Improved the firmware update method by
removing the [UPS has no output]" alarm that the user had to clear after each update.
- Improved the battery aging calculations by
setting the default initial battery running time to 0 days after full-charge at factory.
- Increased the maximum number of possible
connected external temperature sensors to 40.
- Updated the RDU101 interface to report the
UPS ambient temperature.
- Added to the RDU101 interface the reporting
of the UPS alarm [Battery Not Qualified].
- Added to the command line interface
reporting of the number of external battery cabinets.
- Added to the command line interface ability
to set a static IP address on the RDU101 interface.
- Updated the command line interface so the
format of the discharge time is consistent with the LCD; XX hr XX min.
- Added support for YDN23 communications
protocol.
|
September 13, 2019
|
5KVA-10KVA (MV) |
V160 |
V140 |
GXT5(5-10K)(MV)2019-09-13.zip
+
-
|
Release Notes:
- Added LCD pop-up notification message to
detect if the number of external battery cabinets changes.
|
May 15, 2019
|
5KVA-10KVA (MV) |
V150 |
V140 |
GXT5(5-10K)(MV)2019-05-15.zip
+
-
|
Release Notes:
- Updated the LCD displayed Chinese language
shutdown and shutoff menus.
- Updated the RDU101 interface to allow
external battery temperature sensors to be connected after power on.
- Updated the RDU101 interface flow screen to
match LCD.
- Added to the command line interface ability
to configure RDU101 network settings.
- Updated the command line interface to
increase the login timeout from 1 minute to 3 minutes.
|
February 22, 2019
|
5KVA-10KVA (MV) |
V140 |
V140 |
GXT5(5-10K)(MV)2019-02-22.zip
+
-
|
Release Notes:
- Initial release 5KVA-10KVA (MV)
|
Releases for Vertiv Liebert GXT5 VRLA UPS 15KVA-20KVA (MV)
GXT5-15KMVRT11UXLN, GXT5-20KMVRT11UXLN
NOTE: Each release includes all the updates from previous releases.
If upgrading a firmware version that is several releases old, it is only necessary to install the
latest.
For detailed instructions refer to the user guide.
| RELEASE DATE |
PRODUCT
FAMILY |
VERSION |
DOWNLOAD |
| MCU |
DSP |
January 2025
|
15kVA-20kVA
(MV) |
V250 |
V170 |
GXT5LA (15-20K MV)
2025-Jan.zip +
-
|
Release Notes:
- Updated the USB HID protocol mapping to mimic
the GXT4 models
- Changed the default setting of "start with no
battery" to ENABLED
- Improved the battery test feature to address
multiple battery models
- Enabled the Auto-restart feature to function
with no battery detected
|
October 2023
|
15kVA-20kVA
(MV) |
V240 |
V160 |
GXT5LA (15-20K
MV) 2023-Oct.zip +
-
|
Release Notes:
- Improved battery charging logic to automatically
set the charge current and temperature compensation
- Improved battery test logic accuracy for both
automatic & manual tests for all load levels
- Fixed a minor security vulnerability in the CLI
interface
|
October 2022
|
15kVA-20kVA
(MV) |
V230 |
V150 |
GXT5LA
(15-20K MV) 2022-Oct.zip +
-
|
Release Notes:
- Added MODBUS RTU protocol integrated as standard
for all GXT5 VRLA models.
|
May 2022
|
15kVA-20kVA
(MV) |
V210 |
V150 |
GXT5LA
(15-20K MV) 2022-May.zip +
-
|
Release Notes:
- Improved RDU101 web-interface active events log
by removing "UPS Output on Inverter" alert.
|
October 12, 2020
|
15KVA-20KVA
(MV) |
V190 |
V150 |
GXT5(15-20K)(MV)2020-10-12.zip
+
-
|
Release Notes:
- Enhanced the security of the firmware update
procedure by using encrypted firmware files. This prevents the use of potentially
non-authentic firmware.
- Improved the [Max charge curr] setting to only
show valid options for the installed UPS/EBC configuration.
- Added the ability to change the LCD settings
menu and maintenance menu passwords via the CLI.
- Added the ability to execute a delayed shutdown
from 0-999 seconds via the CLI.
- Added Czech language option to the LCD.
- Improved the fan performance by making the speed
more stable and smoothing the transition between speeds.
- Added the DSP firmware kernal version number to
the LCD About tab.
- Improved the displayed load and runtime
sensitivity on light loads down from 5% to 2% load, on the 5K through 20K models.
(GXT5-5000MV, GXT5-6000MV, GXT5-8000MV, GXT5-10KMV)
- Changed the setting name of [Temperature type]
to [Temperature unit].
- Changed the default temperature display from °C
to °F for HV, MV, and LV models.
|
May 30, 2020
|
15KVA-20KVA
(MV) |
V180 |
V160 |
GXT5(15-20K)(MV)2020-05-30.zip
+
-
|
Release Notes:
- Initial release. 15KVA-20KVA (MV)
|
Releases for Vertiv Liebert GXT5 VRLA UPS 5KVA-10KVA (HV, I)
GXT5-5000IRT5UXLN, GXT5-5000IRT5UXLE, GXT5-5000HVRT5UXLN, GXT5-6000IRT5UXLN,
GXT5-6000IRT5UXLE, GXT5-6KL630RT5UXLN, GXT5-8000IRT5UXLN, GXT5-8000IRT5UXLE, GXT5-8000HVRT5UXLN,
GXT5-10KIRT5UXLN, GXT5-10KIRT5UXLE, GXT5-10KHVRT5UXLN
NOTE: Each release includes all the updates from previous releases. If
upgrading a firmware version that is several releases old, it is only necessary to install the latest.
For detailed instructions refer to the user guide.
| RELEASE DATE |
PRODUCT
FAMILY |
VERSION |
DOWNLOAD |
| MCU |
DSP |
January 2025
|
5kVA-10kVA (HV, I) |
V250 |
V180 |
GXT5LA (5-10K HV,I)
2025-Jan.zip +
-
|
Release Notes:
- Updated the USB HID protocol mapping to
mimic the GXT4 models
- Changed the default setting of "start with
no battery" to ENABLED
- Improved the battery test feature to address
multiple battery models
- Enabled the Auto-restart feature to function
with no battery detected
|
October 2023
|
5kVA-10kVA (HV, I) |
V240 |
V170 |
GXT5LA
(5-10K HV,I) 2023-Oct.zip +
-
|
Release Notes:
- Improved battery charging logic to
automatically set the charge current and temperature compensation
- Improved battery test logic accuracy for
both automatic & manual tests for all load levels
- Fixed a minor security vulnerability in the
CLI interface
|
October 2022
|
5kVA-10kVA (HV, I) |
V230 |
V160 |
GXT5LA
(5-10K HV,I) 2022-Oct.zip +
-
|
Release Notes:
- Added MODBUS RTU protocol integrated as
standard for all GXT5 VRLA models.
|
May 2022
|
5kVA-10kVA (HV, I) |
V210 |
V160 |
GXT5LA
(5-10K HV,I) 2022-May.zip +
-
|
Release Notes:
- Improved RDU101 web-interface active events
log by removing "UPS Output on Inverter" alert.
|
November 15, 2021
|
5kVA-10kVA (HV, I) |
V200 |
V160 |
GXT5(5-10K)(HV,I)2021-11-15.zip
+
-
|
Release Notes:
- Added all UPS status and setting datapoints
available on the LCD to the RDU101 web-interface and SNMP/other protocols.
- Added a new user-configurable alarm,
"Replace Battery Soon", which can be set to alert the user 2, 3, or 4 months before the
time the UPS calculates a new battery will be needed, allowing time for replacement
batteries to be ordered.
- Added the ability to adjust [Discharge
protect time] and [Guaranteed Shutdown] settings on the CLI.
- Improved the downloadable 'Event Log.csv' by
replacing the catch-all "General Unspecified Event" with each UPS alarm as reported on
the UPS LCD.
- Fixed an intermittent communication issue
between RDU101 and UPS.
|
October 12, 2020
|
5KVA-10KVA (HV,I) |
V190 |
V160 |
GXT5(5-10K)(HV,I)2020-10-12.zip
+
-
|
Release Notes:
- Enhanced the security of the firmware update
procedure by using encrypted firmware files. This prevents the use of potentially
non-authentic firmware.
- Improved the [Max charge curr] setting to
only show valid options for the installed UPS/EBC configuration.
- Added the ability to change the LCD settings
menu and maintenance menu passwords via the CLI.
- Added the ability to execute a delayed
shutdown from 0-999 seconds via the CLI.
- Added Czech language option to the LCD.
- Improved the fan performance by making the
speed more stable and smoothing the transition between speeds.
- Added the DSP firmware kernal version number
to the LCD About tab.
- Improved the displayed load and runtime
sensitivity on light loads down from 5% to 2% load, on the 5K through 20K models.
(GXT5-5000HV, GXT5-6KL630, GXT5-8000HV, GXT5-10KHV, GXT5-5000I, GXT5-6000I, GXT5-8000I,
GXT5-10KI)
- Changed the setting name of [Temperature
type] to [Temperature unit].
- Changed the default temperature display from
°C to °F for HV, MV, and LV models.
|
May 30, 2020
|
5KVA-10KVA (HV,I) |
V180 |
V150 |
GXT5(5-10K)(HV,I)2020-05-30.zip
+
-
|
Release Notes:
- Changed the user setting and factory default
value of [Guaranteed Shutdown] to "disabled" to reflect the use-case of the majority of
customers.
- Changed the user setting and factory default
value of [Battery Periodic Test] to "enabled" to allow automatic battery self checks.
The default interval for battery self checks is 8 weeks, but this can be changed in the
settings menu.
- Improved the behavior of [Any Mode Shutdown]
by checking the state of the dry contacts during power up after a utility outage and
return. If the contacts are cleared during the outage, the UPS will now power back on
automatically when the utility returns.
- Improved the complete local UPS shutdown
procedure by adding step-by-step instructions to the LCD when a full shutdown is
initiated.
- Added a warning message to the RDU101 web
interface showing when the UPS detects a disconnected external battery cabinet. (RDU101
FW v1.4 required.)
- Added support for Vertiv's new Power Assist
tool.
- Improved the responsiveness of the status
updates reported through the USB HID / Windows OS.
- Added ability to switch the temperature
readings from C to F.
- Added Italian language to the LCD.
- Changed the name of the setting [Battery
Replacement Time] to [Battery Last Replaced] and updated the default time from
2017-12-14:00:00:00 to the date/time of production.
- Corrected the issue where "unavailable" was
being displayed in the [Battery Temperature] field in the RDU101 web interface.
- UpdatedAdded legacy GXT4 datapoints to the
RDU101 interface: BatteryCharger, BatteryFloatVoltage, DeviceManufactureDate. (RDU101 FW
v1.4 required.)
|
November 30, 2019
|
5KVA-10KVA (HV,I) |
V170 |
V140 |
GXT5(5-10K)(HV,I)2019-11-30.zip
+
-
|
Release Notes:
- Updated the factory default setting for
battery charging temperature compensation [temp compensation] from disable to enabled.
Note: This does not change the user setting,
just the factory default setting.
- Improved the firmware update method by
removing the [UPS has no output]" alarm that the user had to clear after each update.
- Improved the firmware update method by
eliminating the connected EBC notification after each update.
- Added the ability to display an overtemp
alarm coming from a connected GXT5 TDU on the GXT5-6KL630RT5UXLN, GXT5-8000HVRT5UXLN,
and GXT5-10KHVRT5UXLN models.
- Improved the battery aging calculations by
setting the default initial battery running time to 0 days after full-charge at factory.
- Increased the maximum number of possible
connected external temperature sensors to 40.
- Added to the RDU101 interface the reporting
of the UPS alarm [Battery Not Qualified].
- Updated the RDU101 interface to report the
UPS ambient temperature.
- Added support for YDN23 communications
protocol.
- Added to the command line interface
reporting of the number of external battery cabinets.
- Added to the command line interface ability
to set a static IP address on the RDU101 interface.
- Updated the command line interface so the
format of the discharge time is consistent with the LCD; XX hr XX min.
|
September 13, 2019
|
5KVA-10KVA (HV,I) |
V160 |
V130 |
GXT5(5-10K)(HV,I)2019-09-13.zip
+
-
|
Release Notes:
- Added LCD pop-up notification message to
detect if the number of external battery cabinets changes
|
May 15, 2019
|
5KVA-10KVA (HV,I) |
V150 |
V130 |
GXT5(5-10K)(HV,I)2019-05-15.zip
+
-
|
Release Notes:
- Initial release. 500VA-3KVA (I, HV)
- Improved the quality of the battery charging
current to allow for better charging performance.
- Improved the diagnostic alarm [auxiliary
power fault].
- Updated the LCD displayed Chinese language
shutdown and shutoff menus.
- Updated the RDU101 interface to allow
external battery temperature sensors to be connected after power on.
- Updated the RDU101 interface flow screen to
match LCD.
- Added to the command line interface ability
to configure RDU101 network settings.
- Updated the command line interface to
increase the login timeout from 1 minute to 3 minutes.
|
February 22, 2019
|
5KVA-10KVA (HV,I) |
V150 |
V130 |
GXT5(5-10K)(HV,I)2019-02-22.zip
+
-
|
Release Notes:
- Improved the firmware update method by
adding a checksum to prevent loading incorrect firmware files to the UPS.
- Improved the battery status and output
overload alarm reporting through the USB HID protocol to Windows operating systems.
- Added the ability of the battery to remain
charging during a RDU101 card firmware update.
- Added to the RDU1010 interface battery
replacement time and increased the precision of battery backup time status.
- Updated the RDU101 interface to remove
paralleling alarms for models that do not support paralleling.
- Added support for I models "E"
configurations.
|
December 22, 2018
|
5KVA-10KVA (HV,I) |
V130 |
V130 |
GXT5(5-10K)(HV,I)2018-12-22.zip
+
-
|
Release Notes:
- Initial release. 5KVA-10KVA (HV, I)
|
Releases for Vertiv Liebert GXT5 VRLA UPS 16KVA-20KVA (I)
GXT5-16KIRT9UXL,
GXT5-20KIRT9UXL
NOTE: Each release includes all the updates from previous releases.
If upgrading a firmware version that is several releases old, it is only necessary to install the
latest. For detailed instructions refer to the user guide.
| RELEASE DATE |
PRODUCT
FAMILY |
VERSION |
DOWNLOAD |
| MCU |
DSP |
January 2025
|
16kVA-20kVA
(I) |
V250 |
V160 |
GXT5LA (16-20K I)
2025-Jan.zip +
-
|
Release Notes:
- Updated the USB HID protocol mapping to mimic
the GXT4 models
- Changed the default setting of "start with no
battery" to ENABLED
- Improved the battery test feature to address
multiple battery models
- Enabled the Auto-restart feature to function
with no battery detected
|
October 2023
|
16kVA-20kVA
(I) |
V240 |
V150 |
GXT5LA (16-20K
I) 2023-Oct.zip +
-
|
Release Notes:
- Improved battery charging logic to automatically
set the charge current and temperature compensation
- Improved battery test logic accuracy for both
automatic & manual tests for all load levels
- Fixed a minor security vulnerability in the CLI
interface
|
October 2022
|
16kVA-20kVA
(I) |
V230 |
V140 |
GXT5LA
(16-20K I) 2022-Oct.zip
+
-
|
Release Notes:
- Added MODBUS RTU protocol integrated as standard
for all GXT5 VRLA models.
|
May 2022
|
16kVA-20kVA
(I) |
V210 |
V140 |
GXT5LA
(16-20K I) 2022-May.zip
+
-
|
Release Notes:
- Improved RDU101 web-interface active events log
by removing "UPS Output on Inverter" alert.
|
October 12, 2020
|
16KVA-20KVA
(I) |
V190 |
V140 |
GXT5(16-20K)(I)2020-10-12.zip
+
-
|
Release Notes:
- Enhanced the security of the firmware update
procedure by using encrypted firmware files. This prevents the use of potentially
non-authentic firmware.
- Improved the [Max charge curr] setting to only
show valid options for the installed UPS/EBC configuration.
- Added the ability to change the LCD settings
menu and maintenance menu passwords via the CLI.
- Added the ability to execute a delayed shutdown
from 0-999 seconds via the CLI.
- Added Czech language option to the LCD.
- Improved the fan performance by making the speed
more stable and smoothing the transition between speeds.
- Added the DSP firmware kernal version number to
the LCD About tab.
- Improved the displayed load and runtime
sensitivity on light loads down from 5% to 2% load, on the 5K through 20K models.
(GXT5-16KI, GXT5-20KI)
- Changed the setting name of [Temperature type]
to [Temperature unit].
- Changed the default temperature display from °C
to °F for HV, MV, and LV models.
|
May 30, 2020
|
16KVA-20KVA
(I) |
V180 |
V130 |
GXT5(16-20K)(I)2020-May-30.zip
+
-
|
Release Notes:
- Changed the user setting and factory default
value of [guaranteed shutdown] to "disabled" to reflect the use-case of the majority of
customers. See user guide for details on this setting.
- Changed the user setting and factory default
value of [battery periodic test] to "enabled" to allow automatic battery self checks.
- Improved the behavior of [any mode shutdown] by
checking the state of the dry contacts during power up after a utility outage and return. If
the contacts are cleared during the outage, the UPS will now power back on automatically
when the utility returns.
- Improved the complete UPS shutdown procedure by
adding step-by-step instructions to the LCD when a full shutdown is initiated.
- Added a warning message to the RDU101 web
interface showing when the UPS detects a disconnected external battery cabinet. (RDU101 FW
v1.4 required.)
- Added support for Vertiv's new Power Assist
tool.
- Improved the responsiveness of the status
updates reported through the USB HID / Windows OS.
- Added ability to switch the temp readings from C
to F.
- Added Italian language to the LCD.
- Changed the name the setting [Battery
replacement time] to [Battery Last Replaced] and updated the default time from
2017-12-14:00:00:00 to the date/time of production.
- Corrected the issue where "unavailable" was
being displayed in the [battery temperature] field in the RDU101 web interface.
- Added legacy GXT4 datapoints to the RDU101
interface: BatteryCharger, BatteryFloatVoltage, DeviceManufactureDate. ( (RDU101 FW v1.4
required.)
|
November 30, 2019
|
16KVA-20KVA
(I) |
V170 |
V120 |
GXT5(16-20K)(I)2019-11-30.zip
+
-
|
Release Notes:
- Added the reporting of the number of external
battery cabinets through the command line interface.
- Updated the format of the discharge time shown
on the command line interface to be consistent with the LCD; XX hr XX min.
- Updated the command line interface networking
setup to allow setting a static IP address to the RDU101 card.
- Set the default initial battery running time to
0 days after full-charge at factory.
- Improved the firmware upgrade method by removing
the "UPS has no output" alarm that the user had to clear after each update.
- Added support for YDN23 communications protocol.
- Added the "Battery Not Qualified" alarm to the
RDU101 interface.
- Added support for Vertiv's new Power Assist
tool.
- Increased the maximum number of possible
connected external temperature sensors to 40.
- Added the temperature reading to the RDU101
interface.
|
September 13, 2019
|
16KVA-20KVA
(I) |
V160 |
V120 |
GXT5(16-20K)(I)2019-09-13.zip
+
-
|
Release Notes:
- Added LCD pop-up notication message if the
number of detected external battery cabinets changes.
|
June 04, 2019
|
16KVA-20KVA
(I) |
V150 |
V120 |
GXT5(16-20K)(I)2019-06-04.zip
+
-
|
Release Notes:
- 16-20KVA I initial release.
|