NetSure HVT EO2 CN1
400V DC Power is designed to ensure the highest levels of efficiency and reliability. Based on flexible architecture, 400V DC power can be implemented at a wide variety of different telecom and data centers sites. Whether your site equipment powering needs include 400V DC, 48V DC, or AC Power - or a combination of all three - 400V DC can be the backbone infrastructure of a cost effective and efficient site design.
Bu Ürün Panonuza Kaydedildi
Bu ürünü, daha sonra görüntülemek üzere panonuza kaydettiniz. Artık kaydedilmesini istemediğinizde ürünü kolayca panonuzdan çıkarabilirsiniz.
Bunu daha sonrası için kaydetmek üzere lütfen oturum açın veya hesap oluşturun
- Veri Merkezi/Sunucu Barındırma/Barındırma
- Telekom
NetSure HVT EO2 CN1
400V DC Power is designed to ensure the highest levels of efficiency and reliability. Based on flexible architecture, 400V DC power can be implemented at a wide variety of different telecom and data centers sites. Whether your site equipment powering needs include 400V DC, 48V DC, or AC Power - or a combination of all three - 400V DC can be the backbone infrastructure of a cost effective and efficient site design.
- Veri Merkezi/Sunucu Barındırma/Barındırma
- Telekom
Avantajlar
Özellikleri
Teknik Özellikler
This efficient, reliable family of AC to DC power systems for critical HVDC power applications combines the proven benefits of 48V DC power – modularity, scalability, ease of integration – with the cable and installation saving benefits of higher voltage distribution.
- Product Overview
- Güç Kapasitesi
- 360 kW
- Akım Kapasitesi
- 900 A
- Çıkış Voltajı, Nominal
- 400 VDC
- Giriş Voltajı, Nominal
- 380 VAC / 480 VAC
- Sistem Tipi
- Cabinet
- Input
- Giriş Voltajı, Nominal
- 380 VAC / 480 VAC
- Giriş Voltajı, İşletimsel
- 260-530 VAC
- Giriş Bağlantıları
- 2 x 3-phase 4-wire / 3-phase 5-wire (Available for 630 , 800 or 1000 A input current
- Equipment Dimensions (H x W x D)
- Battery control box
- Erişim
- Full front access, easy front and rear maintenance, fee cabling.
- Output
- Çıkış Voltajı, Nominal
- 400 VDC
- Çıkış Voltajı, İşletimsel
- 378 VDC
- Çıkış Kapasitesi
- 360 kW / 900 A
- Pik Verimlilik
- 97 %
- Yük Devre Kesicileri / Sigortalar
- Fuses or MCB
- Physical Characteristics
- Akü Devre Kesicileri / Sigortalar
- 2 x 1250 A Fuse or 2 X 1600 A Fuse
- Ağırlık (lb / kg)
- 200-300 kg
- Yükseklik (inç / mm)
- 2000 mm
- Genişlik (inç / mm)
- 600 mm
- Derinlik (inç / mm)
- 800 mm