Releases for Vertiv Liebert GXT5 VRLA UPS 16KVA-20KVA (I)
GXT5-16KIRT9UXL, GXT5-20KIRT9UXL
NOTE: Each release includes all the updates from previous releases. If upgrading a firmware version that is several releases old, it is only necessary to install the latest. For detailed instructions refer to the user guide.
| RELEASE DATE |
PRODUCT FAMILY |
VERSION |
DOWNLOAD |
| MCU |
DSP |
October 2023
|
16kVA-20kVA (I) |
V240 |
V150 |
GXT5LA (16-20K I) 2023-Oct.zip + -
|
Release Notes:
- Improved battery charging logic to automatically set the charge current and temperature compensation
- Improved battery test logic accuracy for both automatic & manual tests for all load levels
- Fixed a minor security vulnerability in the CLI interface
|
October 2022
|
16kVA-20kVA (I) |
V230 |
V140 |
GXT5LA (16-20K I) 2022-Oct.zip + -
|
Release Notes:
- Added MODBUS RTU protocol integrated as standard for all GXT5 VRLA models.
|
May 2022
|
16kVA-20kVA (I) |
V210 |
V140 |
GXT5LA (16-20K I) 2022-May.zip + -
|
Release Notes:
- Improved RDU101 web-interface active events log by removing "UPS Output on Inverter" alert.
|
October 12, 2020
|
16KVA-20KVA (I) |
V190 |
V140 |
GXT5(16-20K)(I)2020-10-12.zip + -
|
Release Notes:
- Enhanced the security of the firmware update procedure by using encrypted firmware files. This prevents the use of potentially non-authentic firmware.
- Improved the [Max charge curr] setting to only show valid options for the installed UPS/EBC configuration.
- Added the ability to change the LCD settings menu and maintenance menu passwords via the CLI.
- Added the ability to execute a delayed shutdown from 0-999 seconds via the CLI.
- Added Czech language option to the LCD.
- Improved the fan performance by making the speed more stable and smoothing the transition between speeds.
- Added the DSP firmware kernal version number to the LCD About tab.
- Improved the displayed load and runtime sensitivity on light loads down from 5% to 2% load, on the 5K through 20K models. (GXT5-16KI, GXT5-20KI)
- Changed the setting name of [Temperature type] to [Temperature unit].
- Changed the default temperature display from °C to °F for HV, MV, and LV models.
|
May 30, 2020
|
16KVA-20KVA (I) |
V180 |
V130 |
GXT5(16-20K)(I)2020-May-30.zip + -
|
Release Notes:
- Changed the user setting and factory default value of [guaranteed shutdown] to "disabled" to reflect the use-case of the majority of customers. See user guide for details on this setting.
- Changed the user setting and factory default value of [battery periodic test] to "enabled" to allow automatic battery self checks.
- Improved the behavior of [any mode shutdown] by checking the state of the dry contacts during power up after a utility outage and return. If the contacts are cleared during the outage, the UPS will now power back on automatically when the utility returns.
- Improved the complete UPS shutdown procedure by adding step-by-step instructions to the LCD when a full shutdown is initiated.
- Added a warning message to the RDU101 web interface showing when the UPS detects a disconnected external battery cabinet. (RDU101 FW v1.4 required.)
- Added support for Vertiv's new Power Assist tool.
- Improved the responsiveness of the status updates reported through the USB HID / Windows OS.
- Added ability to switch the temp readings from C to F.
- Added Italian language to the LCD.
- Changed the name the setting [Battery replacement time] to [Battery Last Replaced] and updated the default time from 2017-12-14:00:00:00 to the date/time of production.
- Corrected the issue where "unavailable" was being displayed in the [battery temperature] field in the RDU101 web interface.
- Added legacy GXT4 datapoints to the RDU101 interface: BatteryCharger, BatteryFloatVoltage, DeviceManufactureDate. ( (RDU101 FW v1.4 required.)
|
November 30, 2019
|
16KVA-20KVA (I) |
V170 |
V120 |
GXT5(16-20K)(I)2019-11-30.zip + -
|
Release Notes:
- Added the reporting of the number of external battery cabinets through the command line interface.
- Updated the format of the discharge time shown on the command line interface to be consistent with the LCD; XX hr XX min.
- Updated the command line interface networking setup to allow setting a static IP address to the RDU101 card.
- Set the default initial battery running time to 0 days after full-charge at factory.
- Improved the firmware upgrade method by removing the "UPS has no output" alarm that the user had to clear after each update.
- Added support for YDN23 communications protocol.
- Added the "Battery Not Qualified" alarm to the RDU101 interface.
- Added support for Vertiv's new Power Assist tool.
- Increased the maximum number of possible connected external temperature sensors to 40.
- Added the temperature reading to the RDU101 interface.
|
September 13, 2019
|
16KVA-20KVA (I) |
V160 |
V120 |
GXT5(16-20K)(I)2019-09-13.zip + -
|
Release Notes:
- Added LCD pop-up notication message if the number of detected external battery cabinets changes.
|
June 04, 2019
|
16KVA-20KVA (I) |
V150 |
V120 |
GXT5(16-20K)(I)2019-06-04.zip + -
|
Release Notes:
- 16-20KVA I initial release.
|